TANK FILL PANEL and STATION
226
   

REMOTE FUEL FILL PANEL
A NEMA 3R enclosure, remotely mounted, used to monitor
fuel fill activities. At 90% fuel fill, alarm horn activates and
light illuminates (alarm horn and silence switch included),
95% alarm horn activates, light illuminates, and an optional
N/O solenoid valve (opt #361) closes allowing no more fuel
to enter tank.

Add Variations:

226FM -  WALL-FLUSH MOUNTING of REMOTE
FUEL FILL PANEL
Necessary brackets (only) that is needed to recess panel
enclosure (except door) into wall.

226PM - ASSISTING PUMP and MOTOR for
REMOTE FUEL FILL PANEL
The controls, brackets, etc. necessary to mount a single
pump and motor to pump fuel to a non-gravity fill main
storage tank.
NOTE: Specify / order pump and motor separately according
to requirements.
 
227
 
SPILL CONTAINER - WALL

Designed for wall mounting, this 7.5 gallon container is
used to prevent over-spill from contaminating soil, floor, etc.  
High speed drain valve included.

Specify One Of These Variations:

227-2 - 2" NPT Outlet Connection
227-3 - 3" NPT Outlet Connection
227-4 - 4" NPT Outlet Connection
229
  DRIP BASIN

A one gallon container, lockable with gasket for manual
filling of Day Tank or Subbase
230

REMOTE FUEL FILL STATION
A lockable, weatherproof, dual-door enclosure designed to accomodate delivery truck
curb-side filling of storage tank via hose connection. Inside are two compartments.
The right side has a 2" Camlok (tm) connector, a check valve, a manual shut-off valve,
and a 7-1/2 containment sump. The left (isolated) side has the electrical components
required to monitor fuel activities and report abnormal conditions. When the tank
being filled reaches a 90% set point, a warning light comes on and an alarm horn
sounds. If filling continues, a second light comes on at 95% capacity and an alarm
horn again sounds. At this time, an optional solenoid valve(opt 361) will close
allowing no more fuel to enter the tank. A silence switch and remote contact outputs
are standard.