HIGH FUEL LEVEL ALARM

A separate float switch which activates a red pilot light on the
control panel when fuel fills beyond a preset level (normally 102%)
.     For Remote Signal (Dry Contacts), Add ...
208
  REMOTE ANNUNICATION
(HIGH FUEL LEVEL ALARM)

Components to provide a heavy-duty, remote signal of High Fuel
Level Alarm (option #207). Dry contact terminal allows connection
of customer supplied device up to 3 amp.
209
  HIGH FUEL LEVEL SWITCH

A separate float switch that activates a remote outgoing signal
when the fuel rises to a predetermined level (normally 102%
capacity).  Includes dry terminal (30-watt) contacts.

213
   
CRITICAL HIGH FUEL ALARM w/PUMP MOTOR
SHUTDOWN
This switch/alarm assembly prevents tank over-filling when the
fuel level reaches a critical high level - normally 3" from the top of
the tank or 103%.

Tanks with a pump / motor system — a separate float switch
activates a red alarm light on the tank control panel, shuts down
pump motor(s), and closes a normally open solenoid valve that is
installed at fuel inlet.  To specify solenoid valve voltage and inlet
pipe size, use option codes 213A thru 213H shown below.

120 vac
1/2” NPT Fuel Line
1” NPT Fuel Line
1-1/2” NPT Fuel Line
2” NPT Fuel Line

12 vdc
1/2” NPT Fuel Line
1” NPT Fuel Line
1-1/2” NPT Fuel Line
2” NPT Fuel Line

24 vdc
1/2” NPT Fuel Line
1” NPT Fuel Line
1-1/2” NPT Fuel Line
2” NPT Fuel Line


Manual-Fill and Sub-Base Tanks (no pump/motor system
installed)
— a separate float switch activates a red alarm pilot
light on the tank control panel.

Specify -  
213M for 120 vac red alarm pilot light,
.                213M-12 for 12 vdc red alarm pilot light, or
.                213M-24 for 24 vdc red alarm pilot light




213A
213B
213C
213D


213E-12
213F-12
213G-12
213H-12


213E-24
213F-24
213G-24
213H-24


213M
222
  HIGH FUEL LEVEL EXPLOSION PROOF SWITCH

An explosion-proof sensor that activates remote outgoing signal
when the fuel rises to a pre-determined level.  Includes dry
terminal (30-watt) contacts.  Terminals located in explosion-proof
box.