TRIM DAY TANKS
|
Pryco TRIM Day Tanks have the same standard features (see below) as its Standard Day Tank counterpart, but has a smaller footprint Each tank is either:
- a basic (non-U/L Listed) design, or
- a U/L Listed (Label #142) design; the U/L Listing is Label 142, File #MH12807 - Aboveground Tank for
Flammable Liquids,
Pryco Tanks are fabricated of heavy gauge steel by certified welders. Each tank complies is tested to 5 psi
The sizes and other characteristics differ between Single Wall Tanks and Double Wall Tanks. For a list of sizes, characteristics, and access to drawings of these tanks, click either:
|
|
|
SINGLE WALL TRIM TANKS
|
|
|
|
or
|
|
|
|
|
|
|
|
|
|
|
DOUBLE WALL TRIM TANKS
|
|
|
|
|
|
|
|
|
|
|
We also have seismic versions available for Standard tanks - Call for specifications.
|
|
|
DOUBLE WALL DAY TANKS A totally enclosed outer shell may be added resulting in a double wall construction. Both the inner and the outer tanks are vented separately and each are pressure tested.
When enclosing a U/L Listed day tank, an additional emergency vent is added to the double wall containment area the same size as the inner tank. (The U/L Listing is “Secondary Containment Aboveground Tank for Flammable Liquids”, File MH12807.)
All day tanks (10 gallon and more capacity), excluding Trim day tanks, have all threaded connections located on the tank top (except the tank overflow and the double wall drain and vent). The inner tank drain is located on the tank top, under the removable cover.
|
|
U/L LISTED TANKS
In addition to the Standard features shown above, all U/L Listed tanks have:
- additional internal reinforcement
- a properly sized emergency vent (see sizes at left)
- a U/L Listed label
RUPTURE BASINS
All day tanks may be set within a Rupture Basin, or Open Top Dike. Rupture basins are available with a minimum
capacity of either 150% or 200% of the inner tank (the vessel where fuel is normally stored). The inner tank is
used to determine rupture basin size.
Single wall day tanks may be set within either a 150% or a 200% rupture basin, whereas, those with double wall
construction will only fit within a 200% minimum capacity rupture basin.
Weatherproof rupture basins are also available.
TANK VENTING
Each tank (and double wall containment area, if applicable) has a 2” Atmospheric Vent.
If the tank is U/L Listed, an Emergency Vent is added. The size of the U/L Emergency Vent depends upon the
wetted surface area of the tank and is shown below. If the tank is U/L Listed and double walled, the same size
Emergency Vent is also added to the double wall containment area.
- 2” - 10—50 Gallons, and
- 3” - 60—100 Gallons
STANDARD FEATURES ON TRIM DAY TANKS
|
- Removable Inspection Plate w/Gasket
- Fuel Level Gauge
- Heavy Duty Float Switch
- “Press-to-Test” Switch
- "Pump Running" Indicator Light
- 1/3 hp Thermally Protected, 120vac, 1ph, 60hz Motor
- 2 gpm Bronze Gear Pump w/Stainless Steel Shafts
- Threaded Pipe Connections for:
- Engine Supply and Return (w/Drop Tubes)
- Atmospheric Vent
- Emergency Vent (If U/L Listed)
- Pump-To-Tank Inlets and Outlets (w/Drop Tubes)
- Overflow (Normally Back to Main Tank)
- Extra 2” Connection Ports
- (2 ports in top of 10 thru 150 gallon tanks [one will be used for option 301, if included];
- 1 port in tank top of 200 gallons and above)
- If Double Wall Secondary Containment, Add:
- An Atmospheric Vent
- An Emergency Vent (If U/L Listed)
- Removable Top Cover
- Epoxy Coating Inside
- Pryco (Medium) Gray Exterior Paint (or an Industrial color of choice)
|
|
|