MANUAL TANKS
Pryco’s MANUAL Day Tanks are similar to Standard Day Tanks, but do not have a pump, motor, and a control system. (Non-U/L
Listed Manual tanks do not have a cover.)  

Like all of Pryco’s tanks, they are available in either a U/L Listed (Label 142, File #MH12807 -
Aboveground Tank for Flammable
Liquids
) or a basic, non-U/L Listed version.

Pryco Tanks are fabricated of heavy gauge steel by  certified welders.   Each tank complies with NFPA 30 and is
tested to 5 psi

They are available in a range of sizes.  Each tank is either:
  •  a basic (non-U/L Listed) design, or
  • a U/L Listed (Label #142) design; the U/L Listing is Label 142, File #MH12807 - Aboveground Tank for
    Flammable Liquids,

The sizes and other characteristics differ between Single Wall Tanks and Double Wall Tanks.  For a list of sizes,
characteristics, and access to drawings of these tanks, click either:
We also have seismic versions available for Standard tanks - Call for specifications.
STANDARD FEATURES ON MANUAL DAY TANKS
  • Removable Inspection Plate w/Gasket
  • Fuel Level Gauge
  • Removable Top Cover
  • Epoxy Coating Inside
  • Pryco (Medium) Gray Exterior Paint (or an
    Industrial color of choice)
  • Threaded Pipe Connections for:
DOUBLE WALL DAY TANKS
A totally  enclosed outer shell may be added  resulting in a double wall construction.  Both the inner and the outer
tanks are vented separately and each are pressure tested.

When enclosing a U/L Listed day tank, an additional emergency vent is added to the double wall containment area
the same size as the inner tank. (The U/L Listing is “Secondary Containment Aboveground Tank for Flammable
Liquids”, File MH12807.)

All day tanks (10 gallon and more capacity), excluding Trim day tanks, have all threaded connections located on the
tank top (except the tank overflow and the double wall drain and vent).  The inner tank drain is located on the tank
top, under the removable cover.
U/L LISTED TANKS
In addition to the Standard features shown above, all U/L Listed tanks have:

  • additional internal reinforcement
  • a properly sized emergency vent (see sizes at left)
  • a U/L Listed label
RUPTURE BASINS
All day tanks may be set within a Rupture Basin, or Open Top Dike.  Rupture basins are available with a minimum
capacity of either 150% or 200%  of the inner tank (the vessel where fuel is normally stored).  The inner tank is
used to determine rupture basin size.  

Single wall day tanks may be set within either a 150% or a 200% rupture basin, whereas,  those with double wall
construction will only fit within a 200% minimum capacity rupture basin.

Weatherproof rupture basins are also available.
TANK VENTING
Each tank (and double wall containment area, if applicable) has a 2” Atmospheric Vent.  

If the tank is U/L Listed, an Emergency Vent is added.  The size of the U/L Emergency Vent depends upon the
wetted surface area of the tank and is shown below.  If the tank is U/L Listed and double walled, the same size
Emergency Vent is also added to the double wall containment area.  
  • 2” - 10—50 Gallons,           
  • 3” - 60—150 Gallons,  
  • 4” - 200—600 Gallons,  and
  • 6” - 700—1000 Gallons
General Specifications and Tank Dimensions of all tank design construction may be shown on a single page arranged by tank size.  Select tank
size (U.S. Gallon capacity) from the buttons below:  NOTE - these pages display measurements in both Imperial (as used in U.S.A.) and in metric.
.
MANUAL DAY TANKS
MANUAL TANK
Characteristics & Drawings
Single Wall Tanks
Double Wall Tanks
   DAY TANK
OPTIONS & PARTS
..      Electrical Options
..      Mechanical Options
..      Pumps
..      Motors
..      Replacement Parts