Pryco MANUAL Day Tanks are similar to
Standard Day Tanks, but do not have a
pump, motor, and a control system. (Non-
U/L Listed Manual tanks do not have a
cover.)
Like all of Pryco’s tanks, they are available
in either a U/L Listed (Label 142, File
#MH12807 - Aboveground Tank for
Flammable Liquids) or a basic, non-U/L
Listed version.
Pryco Tanks are fabricated of heavy
gauge steel by certified welders. Each
tank complies with NFPA 30 and is tested
to 5 psi
|
. Manual Tanks take on a variety of roles other than that of a typical day tank. For example:
- Larger Manual tanks are often used as the system’s main storage tank. In this role, they are normally used
in conjunction with a day tank with pump and controls. (Consider a U/L Listed, double walled version.)
- Smaller versions may be used as a wall-mounted "dry sump" for automatic engine lubrication.
. The only restriction - like all tanks, they must not be utilized as a pressurized vessel.
|
We also have seismic versions available for Manual tanks - Call for specifications.
|
|
|
|
STANDARD FEATURES ON MANUAL TANKS
|
|
- Removable 6½" Square Inspection Plate
w/Gasket
- Fuel Level Gauge
- Four - 1" NPT Threaded Pipe Connections
- One - 2" NPT Threaded Pipe Connection for
Tank Vent
- Tank Drain (Sized To Tank Capacity)
- Lift Lugs (on tanks 50 gallons and over)
- Removable top cover (U/L Listed tanks)
- Epoxy coating inside
- Pryco (medium) Gray exterior paint (or an
industrial color of choice)
|
|
|
|
|
A totally enclosed outer shell may be added resulting in a double wall construction. Both the inner and the outer tanks are vented separately and are pressure tested at 5 psi.
When enclosing a U/L Listed day tank, an additional emergency vent is added to the outer tank the same size as the inner tank. (The U/L Listing is "Secondary Containment Aboveground Tank for Flammable Liquids", File MH12807.)
Day Tanks with a capacity of 25 gallons and more have all threaded connections located on the tank top (except the overflow, drains, and the double wall vent). The inner tank drain is piped through the outer shell.
|
| |
|
|
RUPTURE BASINS FOR MANUAL TANKS
|
|
. In addition to the above features, all U/L Listed . tanks have:
- additional internal reinforcement
- a properly sized emergency vent system
- a U/L Listed label
|
|
All Day Tanks can be set in a Rupture Basin (open top dike), including a tank with double wall construction. See Option 385 for sizes.
A Double Wall or a Rupture Basin may be equipped with an optional Leak Detector that will shut down the pump motor, turn on an alarm light and provide contacts for a remote signal - Options 295 and 395.
|
|
The content of this website is copyrighted (c) 2006 - All rights are reserved. Please refer to our site disclaimer.
|
PY25M - A 25-Gallon Manual Day Tank w/1" Shut-Off Manual
|